GOC1784421 Contractor Rv1
GOC1784421 Contractor Rv1 Preaction System Install Radio Room
PU.DP.Que..8088.29965.C401077
Canada, North West Territories, NT - North Slave Region
Henry Larson Building at 5010 49 Ave, Yellowknife, NT
One Time Only- Delivery Date:Mar 26, 2021
Feb 19, 2021 07:46 AM MST
Not Available
Feb 22, 2021 02:00 PM MST
Yes
Feb 26, 2021 02:00 PM MST
Denise Sandulak
204-333-6294
Denise.Sandulak@bgis.com
The scope of this project will include - Installation of 2" Victaulic 745 Series Pneumatic/Electric Double Interlocked Preaction System, c/w Releasing Panel, Integrated Air Compressor, and additional shutoff valve. The system will require both loss of air pressure from an activated sprinkler, and an alarm signal from the releasing panel from cross zoned detection devices to allow water into the piping. Specific tasks will be included Removal of cap off to existing sprinkler heads and drops as these lines run through the room into the communications area; Installation of a 2" Preaction Cabinet in a location to be confirmed by BGIS. Includes all 110V circuits; Install (2) cross zoned detection devices; The tie in of the releasing panel into the local Notifier FACP. Includes all necessary programming.